24.14.1 Verification of the retention of covers or cover-plates
Forces are gradually applied perpendicular to the mounting surface, in such a way that the
resulting force acting on the centre of the covers, cover-plates, or parts of them is respectively.
– 40 N, for covers, cover-plates or parts of them complying with the tests of 24.17 and
24.18, or
– 80 N, for other covers, cover-plates or parts of them.
The force is applied for 1 min. The covers or cover-plates shall not come off.
The test is then repeated on new specimens, the cover or cover-plate being fitted on the wall
after a sheet of hard material, (1 ± 0,1) mm thick, has been fitted around the supporting frame
as shown in figure 31.
NOTE The sheet of hard material is used to simulate wallpaper and may consist of a number of pieces.
After the test, the specimens shall show no damage within the meaning of this standard.
24.14.2 Verification of the removal of covers or cover-plates
A force not exceeding 120 N is gradually applied, perpendicular to the mounting/supporting
surfaces, to covers, cover-plates or parts of them by means of a hook placed in turn in each
of the grooves, holes, spaces or the like, provided for removing them.
The covers or cover-plates shall come off.
Conform to standard:
IEC 60884-1:2002+A1:2006 figure 31
Technical Parameter:
lTest range:around 250mm;
lHard board:1+/-0.1mm;
lForce range:0-200N;